Heating Coil - Water to Air Heat Pump

 

Coil:Heating:WaterToAirHeatPump:EquationFit

Coil:Heating:WaterToAirHeatPump:ParameterEstimation

 

Used in:

 

  • Zone Water To Air Heat Pump
  • Unitary Water To Air Heat Pump AHU

 

The Water to Air Heat Pump Heating Coil provides access to the EnergyPlus Equation fit (Curve fit) and Parameter Estimation models.

 

General

Name

A unique auto-assigned name identifying name for the coil. Any reference to this coil by another object (typically a Zone Water To Air Heat Pump or a Unitary Water To Air Heat Pump AHU) will use this name.

Coil type

Two types of coil are available:

 

Note: The Coil type selected here must match the setting on the paired Water-to-Air Heat Pump Cooling Coil.

Equation Fit Coil Type Settings

The following settings are required when the Coil type is set to 1-Equation Fit.

General

Rated air flow rate

This numeric field contains the rated volumetric air flow rate on the load side of the heat pump (in m3/s or ft3). This field is autosizable.

Rated water flow rate

This numeric field contains the rated volumetric water flow rate on the source side of the heat pump (in m3/s or gal/min). This field is autosizable.

Gross rated heating capacity

This numeric field contains the gross heating capacity of the heat pump at the rated condition (in W or Btu/hr). The gross heating capacity should not account for the effect of supply air fan heat. This field is autosizable.

Rated heating coefficient of performance (COP)

This numeric field contains the gross rated heating coefficient of performance of the heat pump. The gross rated COP of the heat pump should not account for the effect of supply air fan heat.

Ratio of rated heating capacity to rated cooling capacity

This numeric field contains the ratio of rated heating capacity to the rated cooling capacity. It is used to determine the autosized rated heating capacity from the rated cooling capacity. It is also used to determine the autosized rated cooling capacity when peak heating loads are dominating during sizing calculations. If both this object’s and its associated cooling coil’s capacity are provided by the user, this field not used.

 

Typical values for this field depend on the application in which the coils are used. Some suggested values are 1.23 for water loop applications, 0.89 for ground water applications, and 0.76 for ground loop applications (source: 2021 AHRI directory).

Temperatures

Rated entering water temperature

This setting contains the entering water temperature at which the coil capacity, COP and power are rated at. As such, the coil’s COP should be entered at this temperature. The default value is 20°C (rating temperature for water loop water-to-air heat pumps in ISO-13256-1-1998).

Rated entering air dry-bulb temperature

This setting contains the entering air dry-bulb temperature at which the coil capacity, COP and power are rated at. As such, the coil’s COP should be entered at this temperature. The default value is 20°C (rated temperature for water loop water-to-air heat pumps in ISO-13256-1-1998).

Performance Curves

Heating capacity curve

Select a Quad Linear Performance Curve for the heat pump capacity. The Single Speed Equation-Fit Model for Unitary Water-To-Air Heat Pump under the Air System Compound Component Groups in the Engineering Reference document contains more explanation regarding these coefficients.

Heating power consumption curve

Select a Quad Linear Performance Curve for the heat pump power consumption. The Single Speed Equation-Fit Model for Unitary Water-To-Air Heat Pump under the Air System Compound Component Groups in the Engineering Reference document contains more explanation regarding this.

Parameter Estimation Coil Type Settings

The following settings are required when the Coil type is set to 1-Parameter Estimation. DesignBuilder v2026.1 and later only.